Configuring the fieldbus 
  7.6 Communication via RS485 
Inverter with CU230P-2 Control Units  
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG 
155 
6A hex 
Request not included / task is not supported 
(the valid request identifications can be found 
in table "Request identifications controller → inverter") 
6B hex 
No change access for a controller that is enabled
 
(operating status of the inverter prevents 
a parameter change) 
86 hex 
Write access only for commissioning (p0010 = 15) 
(operating status of the inverter 
prevents a parameter change) 
Know-how protection active, access locked 
C8 hex 
Change request below the currently valid limit 
(change request to a value that lies within 
the "absolute" limits, but is however below the currently valid lower limit) 
C9 hex 
Change request above the currently valid limit
 
(example: a parameter value is too large for 
the inverter power) 
CC hex 
Change request not permitted 
(change is not permitted as the access code is not 
 
 
 
Write the parameter number into the PNU (PKE bit 10 ... 0). 
 ≥ 2000 
- offset. 
Write the parameter number minus the offset into the PNU 
(PKE bit
 10 … 0). 
Write the offset in the page index (IND bit 15 … 8). 
Table 7- 14  Offset and page index of the parameter numbers 
For indexed parameters, you must write the index as hex value into the subindex 
(IND bit 7 … 0).