Configuring the fieldbus
7.6 Communication via RS485
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
157
Write request: Changing the automatic restart mode (p1210)
Parameter p1210 defines the automatic restart mode:
PKE, bit 12 … 15 (AK): = 7
(change parameter value (field, word))
PKE, bit 0 … 10 (PNU): = 4BA hex
(1210 = 4BA hex, no offset, as 1210 < 1999)
IND, bit 815 (page index): = 0 hex
(offset 0
corresponds to 0 hex)
IND, bit 07 (subindex): = 0 hex
(parameter is not indexed)
PWE1, bit 015: = 0 hex
PWE2, bit 015: = 1A hex
(26 = 1A hex)
Figure 7-12 Telegram, to activate the automatic restart with p1210 = 26
Write request: Assign digital input 2 with the function ON/OFF1 (p0840[1] = 722.2)
In order to link digital input 2 with ON/OFF1, you must assign parameter p0840[1] (source,
ON/OFF1) the value 722.2 (DI 2). To do this, you must fill the telegram of the parameter
channel as follows:
PKE, bit 12 … 15 (AK): = 7 hex
(change, parameter value (field, word))
PKE, bit 0 … 10 (PNU): = 348 hex
(840 = 348 hex, no offset, as 840 < 1999)
IND, bit 815 (page index): = 0 hex
(offset 0
0 hex)
IND bit 07 (subindex): = 1 hex
(command data set, CDS1 = index1)
PWE1, bit 015
: =
2D2 hex
(722 = 2D2 hex)
PWE2, bit 1015: = 3f hex
(drive object - for SINAMICS G120, always 63 = 3f hex)
PWE2, bit 09: = 2 hex
(index or bit number of the parameter: DI 2 = r0722.2)
Figure 7-13 Telegram, to assign DI 2 with ON/OFF1