Configuring the fieldbus
7.6 Communication via RS485
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
165
Table 7- 17 Baud rates, transmission times, and delays
Baud rate in bit/s (p2020)
Transmission time per
character (11 bits)
Minimum pause
between two
telegrams (p2024[2])
Maximum pause
between two bytes
(p2024[1])
Note
The factory setting for p2024[1] and p2024[2] is 0. The converter specifies the associated
values depending on the protocol selection (p2030) or the baud rate.
Modbus register and Control Unit parameters
The Modbus protocol contains register or bit numbers for addressing memory. You must
assign the appropriate control words, status words and parameters to these registers in the
slave.
The converter supports the following addressing ranges:
40001 … 40065 Compatible with Micromaster MM436
The valid holding register addressing range extends from 40001 to 40522. Access to other
holding registers generates the fault "Exception Code".
The registers 40100 to 40111 are described as process data.
R"; "W"; "R/W" in the column Modbus access stands for read (with FC03); write (with FC06);