EasyManua.ls Logo

Siemens SINAMICS G120 - Page 171

Siemens SINAMICS G120
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuring the fieldbus
7.6 Communication via RS485
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
171
Table 7- 25 Overview of exception codes
Exception
code
Modbus name
Remark
01 Illegal function code An unknown (unsupported) function code was sent to the
slave.
02
Illegal Data Address
An invalid address was requested.
03
Illegal data value
An invalid data value was detected.
04
Server failure
Slave has terminated during processing.
Maximum processing time, p2024[0]
The slave-response time is the time in which the Modbus master expects a response to a
request. Set the same slave-response time (p2024 [0] in the inverter) in the master and
slave.
Process data monitoring time (setpoint timeout), p2040
"Setpoint timeout" (F1910) is issued by the Modbus if p2040 is set to a value > 0 ms and no
process data is requested within this time period.
The "Setpoint timeout" only applies for access to process data (40100, 40101, 40110,
40111). The "Setpoint timeout" is not generated for parameter data (40200 40522).
Note
Adjust the time (factory setting = 100 ms) depending on the number of slaves and the baud
rate set on
the bus.

Table of Contents

Other manuals for Siemens SINAMICS G120

Related product manuals