Setting functions
8.6 Protection functions
Inverter with CU230P-2 Control Units
266 Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
Parameter for
V/f control
Parameter for
vector control
p1294 p1254
Vdc_max control automatic sensing ON level
(factory setting
p1294: 0, factory setting p1254: PM330/PM240 = 1, PM230 = 0)
Activates or deactivates automatic detection of the switch-on
levels of the Vdc_max control.
0: Automatic detection disabled
1: Automatic detection enabled
p0210 p0210
If p1254 or p1294 = 0, the inverter uses this parameter to
calculate the switch-in thresholds of the Vdc_max control.
Set this parameter to the actual value of the input voltage.
For more information about this function, see the List Manual (function diagrams 6320 and
6220).