Setting functions
8.7 Application-specific functions
Inverter with CU230P-2 Control Units
292 Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
Figure 8-29 Parameters for the load torque monitoring
Table 8- 30 Parameterizing the monitoring functions
p2179
Current limit for no-load detection
If the inverter current is below this value, the message "no load" is output.
Delay time for the "no load" message
Delay time for the "motor locked" message
Delay time for the "motor stalled" message
p1745
Deviation of the setpoint from the actual value of the motor flux as of which the
"motor stalled" message is generated
This parameter is only evaluated as part of encoderless vector control.
Speed-dependent torque monitoring
p2181
Load monitoring, response
Setting the response when evaluating the load monitoring.
0: Load monitoring disabled
>0: Load monitoring enabled
Load monitoring, speed threshold 1
Load monitoring, speed threshold 2
Load monitoring, speed threshold 3
p2185
Load monitoring, torque threshold 1, upper
Load monitoring, torque threshold 1, lower
p2187
Load monitoring, torque threshold 2, upper
Load monitoring, torque threshold 2, lower
Load monitoring, torque threshold 3, upper