Backing up data and series commissioning
9.1 Backing up and transferring settings using a memory card
Inverter with CU230P-2 Control Units
330 Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
Procedure
To safely remove the memory card, proceed as follows:
1.
In the Drive Navigatorselect the following screen form:
2.
Click on the button to safely remove the memory card.
3.
Remove the memory card from the inverter after the appropriate message has
been output.
1.
Go to parameter p9400. If a memory card is correctly
inserted, then p9400 = 1.
2.
Set p9400 = 2 The BOP-2 displays "BUSY" for several
seconds and then jumps to either p9400 = 3 or p9400 =
100.
3.
Bei p9400 = 3 remove the memory card from the inverter.
4.
When p9400 = 100 you must not remove the memory card.
In this case, set p9400 = 2 again.
You have now safely removed the memory card from the inverter.