Alarms, faults and system messages
11.5 List of alarms and faults
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
367
Table 11- 7 The most important alarms and faults
F01018 Power-up aborted more than once
1. Switch the module off and on again.
2. After this fault has been output, the module is booted with the factory
settings.
3. Recommission the inverter.
A01028 Configuration error Explanation: Parameterization on the memory card has been created with
a different type of module (order number, MLFB)
Check the module parameters and recommission if necessary.
F01033 Switching over units: Reference
Set the value of the reference parameter not equal to 0.0 (p0304, p0305,
p0310, p0596, p2000, p2001, p2002, p2003, r2004).
F01034 Switching over units: Calculation of
the parameter values after
reference value change
Select the value of the reference parameter so that the parameters
involved can be calculated in the per unit notation (p0304, p0305, p0310,
p0596, p2000, p2001, p2002, p2003, r2004).
The maximum computing power of the control unit was exceeded. The
following measures reduce the load on the control unit:
• Use only one data record (CDS and DDS)
• Only use the safety features of the basic functions
• Deactivate the technology controller
• Use the simple ramp-function generator rather than the extended
ramp-function generator
• Do not use any free function components
• Reduce the sampling time of the free function blocks
F01054 System limit exceeded
F01122 Frequency at the probe input too
Reduce the frequency of the pulses at the probe input.
Motor maintenance interval lapsed
Carry out maintenance and reset the maintenance interval (p0651).
A01900 PROFIBUS: Configuration
telegram faulty
Explanation: A PROFIBUS master is attempting to establish a connection
with a faulty configuration telegram.
Check the bus configuration on the master and slave side.
A01910
F01910
Setpoint timeout The alarm is generated when p2040 ≠ 0 ms and one of the following
causes is present:
• The bus connection is interrupted
• The Modbus master is switched off
• Communications error (CRC, parity bit, logical error)
• An excessively low value for the fieldbus monitoring time (p2040)
A01920 PROFIBUS: Cyclic connection
interrupt
Explanation: The cyclic connection to PROFIBUS master is interrupted.
Establish the PROFIBUS connection and activate the PROFIBUS master
F03505 Analog input, wire break Check the wiring for interruptions.
Check the level of the injected signal.
The input current measured by the analog input can be read out in r0752.