Table 12- 33 PM240-2, PT, Frame Sizes B, 3 AC 380 V … 480 V
Order No. - without filter
Order No. - with filter
...1PE21-8UL0
...1PE21-8AL0
LO power
LO input current
7.5 kW
22.2 A
HO power
HO input current
5.5 kW
19.8 A
Fuse according to IEC
3NE 1803-0 (35 A)
Power losses without filter
kW
1)
1)
Required cooling air flow
Cross section of line and motor cables 1.5 … 6 mm
2
Tightening torque for line and motor cables
Weight without filter
3.6 kg
0.08 kW via heat sink;
Table 12- 34 PM240-2, IP20, Frame Sizes C, 3 AC 380 V … 480 V
Order No. - without filter
Order No. - with filter
LO power
LO input current
11.0 kW
32.6 A
15.0 kW
39.9 A
HO power
HO input current
7.5 kW
27.0 A
11.0 kW
36.0 A
Fuse according to IEC
3NE 1817-0 (50 A)
3NE 1817-0 (50 A)
Power losses without filter
kW
kW
Required cooling air flow
Cross section of line and motor cables 6 …16 mm
2
6 …16 mm
2
Tightening torque for line and motor cables
Weight without filter
4.7 kg
4.8 kg