Technical data
12.2 Technical data, Power Modules
Inverter with CU230P-2 Control Units
410 Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
PM330 frame sizes GX, 3-ph. 380 VAC… 480 VAC
Table 12- 43 PM330 frame sizes GX, 3 AC 380 V … 480 VAC
Rated input current
- for 380/400 V, 40 °C
- for 480 V, 40 °C
- for 380/400 V, 50 °C
317 A
262 A
269 A
375 A
314 A
319 A
Rated output current I
N
- for 380/400 V, 40 °C
- for 480 V, 40 °C
- for 380/400 V, 50 °C
300 A
245 A
255 A
370 A
308 A
315 A
LO power
LO input current
160 kW
314 A
200 kW
369 A
HO power
HO input current
132 kW
257 A
160 kW
302 A
Fuse according to IEC
manufacturer:
Maximum permissible line short-circuit current I
kmax
Minimum permissible line short-circuit current I
kmin
3NE1333-2
Siemens AG
≤ 100 kA
3NE1334-2
Siemens AG
≤ 100 kA
Fuse according to UL
1)
Class J
400 A / 600 V
Class J
500 A / 600 V
N
Required cooling air flow
Maximum connectable cross-section of the line,
2 x 240 mm
2
2 x 240 mm
2
Recommended cable cross-section for 380/400 V
- power cable
2 x 120 mm
2
2 x 120 mm
2
Recommended cable cross-section for 480 V
- power cable
2 x 95 mm
2
2 x 120 mm
2
Tightening torque for line, motor and ground cable
1)
When semi-conductor fuses are used, they must be mounted in the same lower-level construction as the inverter.