Installing
4.5 Connecting inverters in compliance with EMC
Inverter with CU230P-2 Control Units
72 Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
EMC-compliant wiring of Power Modules in degree of protection IP55 / UL type 12
The following diagram shows the EMC-compliant installation of Power Modules with degree
of protection IP55 / UL type 12.
Figure 4-10 EMC-compliant connection of the Power Module PM230, degree of protection IP55 / UL
Type 12
Note
You must use a shielded cable if you use the control terminals of the Control Unit. Connect
the shield to the gland plate via an EMC screw.