Commissioning
5.4 Basic commissioning
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
87
Adapting the PROFINET interface
If you commission the inverter with STARTER via PROFINET, then you must correctly
address your PC and allocate STARTER the interface via which it goes online with the
inverter.
Procedure
To address the inverter, proceed as follows:
1.
Establish the bus connection.
See Section Communication
via PROFINET (Page 108))
2.
From the control panel, assign
the IP address and the subnet
mask address to your
computer:
3.
Go to "Start/Settings/Control
Panel".
4.
Select "Network
Connections".
5.
Right-click to open the
properties window of the LAN
connection.
6.
In this window, select
"Internet Protocol (TCP/IP)".
7.
Select "Properties".
8.
Set 192.168.0.100 as the IP
address of the supervisor and
255.255.255.0 as subnet
mask.
In the company network it is
possible that the IP address
and the subnet mask have
different values. You can
obtain these values from your
network administrator.
9.
Open the SIMATIC Manager.
10.
Assign the TCP/IP interface to
"Intel(R) PRO/100 VE
Network Connection" via
"Tools/PG/PC interface".
You have allocated your computer the IP address and the address of the subnet mask, and
defined the PC interface via which STARTER goes online with the inverter.