Description Of Specific Functions 115
V560 Series High Performance Closed-Loop Vector Inverter User Manual
The frequency set value is given by the process PID output. This option is mainly for the system in which the
PID running output needs to be combined with other setting channel for running. In general running system,
this value does not need to be selected. PID output will automatically participate in setting competition
according to the frequency setting priority.
24: Compensation PID output
The frequency set value is given by the compensation PID output. This option is mainly for the system in
which compensation PID running output needs to be combined with other setting channel for running. In
general running system, this value does not need to be selected. The compensation PID output will
automatically participate in setting competition according to the frequency setting priority.
25: Disturbance running frequency
The frequency set value is given by the disturbance running frequency. This option is mainly for the system in
which the disturbance running output needs to be combined with other setting channel for running. In general
running system, this value does not need to be selected. The disturbance output will automatically participate
in setting competition according to the frequency setting priority.
26: Auto preset speeds
The frequency set value is given by the multi-stage running frequency. This option is mainly for the system in
which the multi-stage running output needs to be combined with other setting channel for running. In general
running system, this value does not need to be selected. The multi-stage running output will automatically
participate in setting competition according to the frequency setting priority.
27: Preset speeds via terminals
The frequency set value is determined by the combination status of the four multifunctional input terminals
(Function No. 1, 2, 3, 4), and the terminal function is set by the parameters F3.0.00~F3.0.08.This way allows
for multi-stage frequency running.
28: Simulated analog input SAI1
29: Simulated analog input SAI2
The frequency setting source and set value are determined by the virtual input parameter Group F4.4.50 ~
F4.4.54.
F0.2.27 Min frequency
channel 1
Setting range: 0.0Hz~[F0.2.28] Factory default: 0.0
F0.2.28 Max frequency
channel1
Setting range: [F0.2.27]~[F0.1.20] Factory default: 50.00
F0.2.30 Min frequency
channel 2
Setting range: 0.0Hz~[F0.2.31] Factory default: 0.0
F0.2.31 Max frequency
channel 2
Setting range: [F0.2.30]~[F0.1.20] Factory default: 50.00
This group of parameters confines the range of frequency allowed to be set for two frequency setting
sources.
F0.2.29 Keypad incremental
value channel 1
Setting range: 0.0Hz~[F0.2.28] Factory default: 0.0
F0.2.32 Keypad incremental
value channel 2
Setting range: 0.0Hz~[F0.2.31] Factory default: 0.0
The frequency command value at the time of panel digital setting can be directly modified with the ▲, ▼ keys
(or shuttle) on the panel in the normal monitoring mode, and the set frequency can be also modified by
means of parameter modification.