114 Description Of Specific Functions
V560 Series High Performance Closed-Loop Vector Inverter User Manual
10: Analog input Al2
The frequency set value is given via the analog input AI2; For relevant characteristics please see the
instructions of the parameters F4.0.02 and F4.0.03.
11: Analog input Al3
The frequency set value is given via the analog input AI3; For relevant characteristics please see the
instructions of the parameters F4.0.04 and F4.0.05.
12: AI1 bipolar setting
The frequency set value is given by the bipolarity of the analog AI1 ([F4.0.00]~[F4.0.01]), and AI1 contains
the direction changing information. For relevant characteristics please see the instructions of the parameters
F4.0.00 and F4.0.01.
13: AI3 bipolar setting
The frequency set value is given by the bipolarity of the analog AI3 ([F4.0.04]~[F4.0.05]), and AI3 contains
the direction changing information. For relevant characteristics please see the instructions of the parameters
F4.00.04 and F4.00.05.
14: Pulse follower input
The frequency set value is given by the pulse input Fin.
15: Pulse follower bipolar input
The frequency set value is given by the pulse input Fin bipolarity, and the pulse signal contains the direction
changing information.
16: MODBUS communications 1 relative (relative set value)
The frequency set value is given by the principal computer through MODBUS fieldbus (RS485
communication port), and the set value (-10000 ~ 10000) is relative data and is corresponding to the upper
limiting frequency.
17: MODBUS communication 2 absolute (absolute set value)
The frequency set value is given by the principal computer through MODBUS fieldbus (RS485
communication port), and the set value (-30000 ~ 30000) is absolute value neglecting the decimal point) (e.g.
the value 1500 corresponds to the set frequency 150.00Hz in general mode.)
18: AI1+AI2
The frequency set value = the frequency value corresponding to the analog input AI1 + the frequency value
corresponding to the analog input AI2
19: AI2+AI3
The frequency set value = the frequency value corresponding to the analog input AI2 + the frequency value
corresponding to the analog input AI3
20: AI2+pulse input Fin
The frequency set value = the frequency value corresponding to the analog input AI2 + the frequency value
corresponding to the pulse input Fin
21: AI1*AI2/full scale of AI2 (10V)
The frequency set value = the frequency value corresponding to AI1 *the frequency value corresponding to
AI2/the frequency corresponding to the maximum input of AI2.
22: AI1/AI2
The frequency set value= the frequency value corresponding to AI1/the frequency value corresponding to
AI2.