230 EMC
V560 Series High Performance Closed-Loop Vector Inverter User manual
1, Performance index of AC output reactor
Rated operational voltage: 380V/50Hz
Dielectric strength: cored winding 3000VAC/50Hz/10mA/60S, no flashover breakdown
Insulation resistance: cored winding 1000VDC, insulation resistance 100MΩ;
Reactor noise is less than 65dB (test at the point of 1m horizontal distance with reactor).
2, Parameter Configuration of AC Output Reactor
Inverter Power
(KW)
Reactor Model
Size L*W*H
(mm)
Mounting
Dimension (mm)
Terminal
Aperture (mm)
0.7 AKSG10A/9V 140*85*140 75*55
1.1 AKSG10A/9V 140*85*140 75*55 φ6
1.5 AKSG10A/9V 140*85*140 75*55 φ6
2.2 AKSG10A/9V 140*85*140 75*55 φ6
3.0 AKSG10A/9V 140*85*140 75*55 φ6
4.0 AKSG15A/9V 140*85*140 75*55 φ6
5.5 AKSG15A/9V 140*85*140 75*55 φ6
7.5 AKSG20A/9V 140*85*140 75*55 φ6
9.0 AKSG30A/9V 210*165*170 110*85 Φ8
11 AKSG30A/9V 210*165*170 110*85 Φ8
15 AKSG40A/9V 210*165*170 110*85 Φ8
18.5 AKSG50A/9V 210*165*170 110*85 Φ8
22 AKSG60A/9V 210*165*170 110*85 Φ8
30 AKSG80A/9V 270*190*230 155*100 Φ10
37 AKSG110A/9V 270*190*230 155*100 Φ10
45 AKSG125A/9V 270*190*230 155*100 Φ10
55 AKSG150A/9V 290*200*230 170*115 Φ10