18-9
IM 05P02C41-01EN
Parameters
18
SELECTParameterMenu(Menu:CS)
Parameter
symbol
Name
Display
level
Settingrange Initialvalue
CS10to
CS19
SELECT parameter
10 to 19
EASY
Setting range of a registered
parameter.
-
ProgramPatternSettingMenu(Menu:PROG>PTNO.(=01to30(99whentheoption
“/AP”isspecified))>SEGNO.(=00))
Parameter
symbol
Name
Display
level
Settingrange Initialvalue
SSP
Starting target
setpoint
EASY
0.0 to 100.0% of PV input range
(EU) (Setting range: P.RL to P.RH)
P.RL
STC Start code EASY
SSP: Program operation begins
with the starting target setpoint.
RAMP:Ramp-prioritizedPVstart
TIME:Time-prioritizedPVstart
LSP: Local-mode start
RSP: Remote-mode start
* STC=TIME cannot be selected
when the parameter SEG.T is
TM.RT.
SSP
WT.SW1to
WT.SW5
Wait function ON/
OFF 1 to 5
STD
OFF: Disable
ON: Enable
OFF
WZ.UP1to
WZ.UP5
Upper-side wait
zone1to5
STD
0.0 to 10.0% of PV input range (EU)
0.5% of PV
input range
WZ.LO1to
WZ.LO5
Lower-side wait
zone1to5
STD
0.5% of PV
input range
WT.TM1to
WT.TM5
Wait time 1 to 5 STD
OFF: No function
0.00 to 999.59 (“hour.minute” or
“minute.second”)
* Available only for the wait time
at the segment switching.
* Use the parameter TMU to set
the time unit. (Common in the
instrument.)
OFF
R.CYCL
Number of repeat
cycles
STD
0 to 999, CONT (The controller
indenitelyrepeatsthesegment
speciedbytheR.STRTand
R.END parameters.)
0
R.STRT
Repeat cycle start
segment number
STD
1 to 99
1≤R.STRT≤R.END≤99
1
R.END
Repeat cycle end
segment number
STD 1
When the program pattern-2 retransmission is selected (PT2.G=ON), the second loop is also
displayed for the parameter SSP. (LP2 lamp is lit.)
18.2ListofParameters