ELECTRICAL DATA 61 62 63
Unit Data DCF058DX-12DVV0 DCF062DX-12FVW0 DCF065DX-12FWW0
Nominal Run Amps (1) A 397.6 409.7 421.8
Maximum Start Amps A 665.0 673.1 657.2
Recommended Mains Fuse Size A 450 450 450
Evaporator
Immersion Heater Rating W 170 170 170
Condenser Fan - Per Fan (EC)
Quantity 12 12 12
Full Load Amps A 3.9 3.9 3.9
Motor Rating kW 2.6 2.6 2.6
Compressor - Per Compressor
Nominal Run Amps A 55.2 / 55.2 55.2 / 59.2 59.2 / 59.2
Quantity 3 + 3 3 + 3 3 + 3
Motor Rating kW 33.1 / 33.1 33.1 / 36.2 36.2 / 36.2
Sump Heater Rating W 140 140 140
Start Amps (2) A 326 / 326 326 / 298 298 / 298
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98) (3)
Nominal Run Amps A 368.5 382.1 395.8
Reactive power reduction/saving (4) kVAr 51.0 48.9 46.8
Maximum Start Amps A 635.9 645.5 631.2
Recommended Mains Fuse Size A 450 450 450
Electronic Soft-start
Nominal Run Amps A 397.6 409.7 421.8
Maximum Start Amps A 534.6 542.7 538.0
Recommended Mains Fuse A 450 450 450
Power Factor Correction (PF
0.98) & Electronic Soft Start (3)
Nominal Run Amps A 368.5 382.1 395.8
Maximum Start Amps A 505.5 515.1 512.0
Recommended Mains Fuse Size A 450 450 450
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 21.2 21.2 21.2
Unit Nominal Run Amps A 418.7 430.8 442.9
Recommended Mains Fuse Size A 450 450 500
Motor Rating kW 12.1 12.1 12.1
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 28.5 28.5 28.5
Unit Nominal Run Amps A 426.0 438.1 450.2
Recommended Mains Fuse Size A 450 500 500
Motor Rating kW 16.4 16.4 16.4
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 19.8 19.8 19.8
Unit Nominal Run Amps A 413.5 425.6 437.8
Recommended Mains Fuse Size A 450 450 500
Motor Rating kW 12.4 12.4 12.4
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 26.9 26.9 26.9
Unit Nominal Run Amps A 419.1 431.3 443.6
Recommended Mains Fuse Size A 450 500 500
Motor Rating kW 16.8 16.8 16.8
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet