ELECTRICAL DATA 64 65 66
Unit Data DCF050DX-13DXY0 DCF053DX-13DPY0 DCF055DX-14DPV0
Nominal Run Amps (1) A 316.2 326.6 354.8
Maximum Start Amps A 591.8 590.0 618.2
Recommended Mains Fuse Size A 355 355 400
Evaporator
Immersion Heater Rating W 170 170 170
Condenser Fan - Per Fan (EC)
Quantity 13 13 14
Full Load Amps A 3.9 3.9 3.9
Motor Rating kW 2.6 2.6 2.6
Compressor - Per Compressor
Nominal Run Amps A 36 / 47.9 59.2 / 47.9 59.2 / 55.2
Quantity 3 + 3 2 + 3 2 + 3
Motor Rating kW 22.7 / 29.8 36.2 / 29.8 36.2 / 33.1
Sump Heater Rating W 140 140 140
Start Amps (2) A 210 / 326 298 / 326 298 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98) (3)
Nominal Run Amps A 304.4 310.5 331.7
Reactive power reduction/saving (4) kVAr 22.7 30.0 41.2
Maximum Start Amps A 580.0 573.9 595.1
Recommended Mains Fuse Size A 355 355 400
Electronic Soft-start
Nominal Run Amps A 316.2 326.6 354.8
Maximum Start Amps A 461.4 459.6 487.8
Recommended Mains Fuse A 355 355 400
Power Factor Correction (PF
0.98) & Electronic Soft Start (3)
Nominal Run Amps A 304.4 310.5 331.7
Maximum Start Amps A 449.6 443.5 464.7
Recommended Mains Fuse Size A 355 355 400
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 14.8 14.8 14.8
Unit Nominal Run Amps A 330.7 341.2 369.5
Recommended Mains Fuse Size A 355 400 400
Motor Rating kW 8.4 8.4 8.4
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 21.2 21.2 21.2
Unit Nominal Run Amps A 337.1 347.6 375.9
Recommended Mains Fuse Size A 355 400 400
Motor Rating kW 12.1 12.1 12.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 13.9 13.9 13.9
Unit Nominal Run Amps A 327.7 337.9 365.9
Recommended Mains Fuse Size A 355 400 400
Motor Rating kW 8.6 8.6 8.6
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 19.8 19.8 19.8
Unit Nominal Run Amps A 332.6 342.8 370.8
Recommended Mains Fuse Size A 355 400 400
Motor Rating kW 12.4 12.4 12.4
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet