DeltaChill™ Air Cooled and FreeCool
144
Chiller Technical Manual 7267818 V1.13.0_01_2018
Air Cooled
Ambient (°C)
Model
Supply
Temp
°C
25°C 30°C 35°C 40°C
Output Input Output Input Output Input Output Input
kW kW kW kW kW kW kW kW
108
DCC052DR-12EYY0
5 534.4 138.9 510.3 153.2 483.0 169.5 452.8 187.8
6 550.1 139.8 525.5 154.2 497.6 170.5 466.4 188.7
7 566.1 140.8 540.9 155.1 511.8 171.3 480.5 189.7
8 582.1 141.7 556.5 156.1 526.8 172.3 494.8 190.7
9 598.3 142.7 572.3 157.1 542.1 173.3 509.4 191.7
10 614.7 143.7 588.2 158.1 557.5 174.4 524.1 192.8
109
DCC054DR-11DYV0
5 560.7 146.8 534.5 162.0 505.4 179.4 473.2 198.9
6 577.4 147.9 550.7 163.0 520.9 180.5 487.6 199.9
7 594.5 149.0 567.3 164.2 536.5 181.6 502.3 200.9
8 611.5 150.0 583.6 165.2 552.4 182.7 517.1 201.9
9 628.8 151.2 600.4 166.4 568.6 183.8 532.3 203.0
10 646.3 152.3 617.4 167.5 584.9 185.0 547.6 204.1
110
DCC058DR-12DVV0
5 589.6 149.6 561.7 165.3 530.1 183.2 495.8 203.6
6 607.4 150.7 578.3 166.2 546.5 184.3 511.3 204.7
7 625.4 151.8 595.7 167.3 563.2 185.4 527.1 205.8
8 643.6 152.9 613.9 168.6 580.1 186.5 543.2 206.9
9 662.0 154.0 631.3 169.6 597.3 187.7 559.6 208.1
10 680.7 155.2 649.4 170.8 614.7 188.9 576.3 209.2
111
DCC060DR-12DVW0
5 618.3 161.3 589.3 178.1 556.8 197.4 520.8 219.0
6 636.3 162.4 606.7 179.2 573.7 198.6 536.6 220.1
7 654.9 163.6 624.7 180.4 590.9 199.8 552.6 221.2
8 673.6 164.8 643.1 181.7 608.4 201.0 568.9 222.3
9 692.6 166.1 661.3 182.9 626.1 202.3 585.5 223.5
10 711.7 167.3 679.9 184.2 644.0 203.6 602.3 224.7
112
DCC063DR-12DWW0
5 658.4 173.7 628.0 191.7 593.4 212.3 554.5 235.0
6 678.4 175.2 646.7 193.1 611.3 213.6 570.8 236.1
7 697.5 176.4 665.7 194.4 629.4 215.0 587.4 237.3
8 717.4 177.7 684.9 195.8 647.9 216.4 604.2 238.4
9 737.5 179.1 704.3 197.2 666.6 217.8 621.2 239.6
10 757.8 180.5 724.0 198.6 685.2 219.1 638.5 240.9
1 Output kW refers to the chilled water duty.
2 Input kW refers to the unit input power (compressor + fans).
3 Duties applicable for chilled water ∆T between 4 and 8°C.
4 Interpolate for water temperatures between those quoted, do not extrapolate.
5 Water ow rate (l/s) = Output ÷ (Cp x ∆T)
6 For conditions outside of those quoted please refer to Airedale.
DCC Performance Data EC Fans