DeltaChill™ Air Cooled and FreeCool
209
Chiller Technical Manual 7267818 V1.13.0_01_2018
Air Cooled
ELECTRICAL DATA 167 168 169
Unit Data DCC077TX-18GYYY DCC080TX-17GYVV DCC083TX-18GVVV
Nominal Run Amps (1) A 523.4 568.0 596.5
Maximum Start Amps A 799.0 835.4 863.9
Recommended Mains Fuse Size A 560 630 630
Evaporator
Immersion Heater Rating W 250 250 250
Condenser Fan - Per Fan (EC)
Quantity 18 17 18
Full Load Amps A 3.9 3.9 3.9
Motor Rating kW 2.6 2.6 2.6
Compressor - Per Compressor
Nominal Run Amps A 47.9 / 47.9 / 47.9 47.9 / 55.2 / 55.2 55.2 / 55.2 / 55.2
Quantity 3 + 3 + 3 3 + 3 + 3 3 + 3 + 3
Motor Rating kW 29.8 / 29.8 / 29.8 29.8 / 33.1 / 33.1 33.1 / 33.1 / 33.1
Sump Heater Rating W 140 140 140
Start Amps (2) A 326 / 326 / 326 326 / 326 / 326 326 / 326 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98) (3)
Nominal Run Amps A 500.7 531.5 552.7
Reactive power reduction/saving (4) kVAr 42.8 65.2 76.5
Maximum Start Amps A 776.3 798.9 820.1
Recommended Mains Fuse Size A 560 630 630
Electronic Soft-start
Nominal Run Amps A 523.4 568.0 596.5
Maximum Start Amps A 668.6 705.0 733.5
Recommended Mains Fuse A 560 630 630
Power Factor Correction (PF
0.98) & Electronic Soft Start (3)
Nominal Run Amps A 500.7 531.5 552.7
Maximum Start Amps A 645.9 668.5 689.7
Recommended Mains Fuse Size A 560 630 630
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 11.2 11.2 11.2
Unit Nominal Run Amps A 534.3 579.0 607.5
Recommended Mains Fuse Size A 560 630 630
Motor Rating kW 6.2 6.2 6.2
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 21.2 21.2 21.2
Unit Nominal Run Amps A 544.3 589.0 617.6
Recommended Mains Fuse Size A 560 630 670
Motor Rating kW 12.1 12.1 12.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 10.2 10.2 10.2
Unit Nominal Run Amps A 531.7 576.2 604.6
Recommended Mains Fuse Size A 560 630 630
Motor Rating kW 6.4 6.4 6.4
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 19.8 19.8 19.8
Unit Nominal Run Amps A 539.6 583.9 612.3
Recommended Mains Fuse Size A 560 630 670
Motor Rating kW 12.4 12.4 12.4
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold
DCC Electrical Data - Extra Quiet