Table 40: Setup Restart
Name
Location
Description
ManualStartOnly
Home Screen ->
Settings ->
Menu ->
ManualStartOnly
ManualStartOnly is a global
restart enable.
ManualStartOnly = True
Drive can only be started by
pressing the Start button on the
keypad.
ManualStartOnly = False
Drive can be started by the
keypad Start button, SCADA
start commands, Autostart on
Power Up, and restarts from
any trigger.
Global Restart
Home Screen ->
Settings ->
Menu ->
Other Initial Setup ->
Global Restart
By default, all triggers have their
Restart delay set to the Global
Restart Time. Best practice is to
set the Global Restart time to the
normal restart time on the drive
(for an ESP system, this is likely
the fluid fallback backspin time).
Restarts/Allowed
Trigger Info Screen
Every Stop trigger can be set to
allow restarts. Restarts/Allowed
is shown as x/y on the trigger
info screen. The y is the number
of restarts allowed. X is the
number of restarts that have been
attempted. Setting the allowed
restart to 0 disables restarts for
that trigger.
By default, all triggers have 0
allowed restarts.