Figure 204: Pump Curve Setup Menu
Set the parameters in this menu to configure Pump Curve Thrust Limits.
•
Upthrust Fault %: Sets the fault level as a % of the range between the pump BEP and the top of the
operational range. Set to 100% to use the operational range as the thrust limit. The default value is 100%.
•
Upthrust Alarm %: Sets the alarm level as a % of the range between the pump BEP and the top of
the operational range. The default value is 75%.
•
Downthrust Fault % and Downthrust Alarm % are set as a % of the range between the pump BEP and
the bottom of the operational range.
•
Each fault/alarm has a trip delay. Set the value to be the time to tolerate the condition before
alarming/faulting.