Communications
338
890053-00-02
10.5.3.2 Binary Output
The output point map controlling the inverter from the Metasys-N2 master.
No.
Name
Range
Description
BO1
Stop Command
1: Stop
Stop command
BO2
Run Forward Command
1: Forward Run
Forward run command
BO3
Run Reverse Command
1: Reverse Run
Reverse run command
BO4
Reset Fault
1: Reset
Fault reset command
BO5
Free-Run Stop
1: Bx
Free-run stop command
10.5.3.3 Analog Input
Metasys-N2 master monitors inverter state.
No.
Name
Unit
Description
AI1
Output Current
Amps
Output current
AI2
Output Frequency
Hz
Output frequency
AI3
Output Speed
RPM
Output speed
AI4
Trip Code
-
Trip code information
(Refer to Common Area parameter address 0h000F)*
AI5
Latch Trip Info1
-
‘Latch’ type fault information 1
(Refer to Common Area parameter address 0h0330)*
AI6
Latch Trip Info2
-
‘Latch’ type fault information 2
(Refer to Common Area parameter address 0h0331)*
AI7
Latch Trip Info3
-
‘Latch’ type fault information 3
(Refer to Common Area parameter address 0h0335)*
AI8
Level Trip Info
-
‘Level’ type fault information
(Refer to Common Area parameter address
0h0332)(1)
AI9
H/W Diagnosis Trip
Info
-
H/W Diagnosis fault information
(Refer to Common Area parameter address
0h0333)(1)
AI10
Warning Info
-
Warning information
(Refer to Common Area parameter address
0h0334)(1)
* Refer to Compatible Common Area Parameter page 311.