10.5.3.4 Binary Input
Metasys-N2 master unit monitors the inverter input and output status in binary codes. The following
table lists the binary codes used and their meanings.
No.
Name
Description
BI1
Stopped
1 Stopped
BI2
Running Forward
1 Forward operation is running.
BI3
Running Reverse
1 Reverse operation is running.
BI4
Tripped
1 Fault occurred.
BI5
Accelerating
1 Accelerating
BI6
Decelerating
1 Decelerating
BI7
Reached Full Speed
1 Running at a steady speed (frequency
reference)
BI8
DC Braking
1 Running on DC power source
BI9
Stopping
1Stopping is in progress.
BI10
P1 Input
1True / 0 - False
BI11
P2 Input
1True / 0False
BI12
P3 Input
1True / 0False
BI13
P4 Input
1True / 0False
BI14
P5 Input
1True / 0False
BI15
P6 Input
1True / 0False
BI16
P7 Input
1True / 0False
BI17
Relay1 State
1On / 0 - Off
BI18
Relay2 State
1On / 0 - Off
BI19
Relay3 State
1On / 0 - Off
BI20
Relay4 State
1On / 0 - Off
BI21
Relay5 State
1On / 0 - Off
BI22
Q1 (OC1) State
1On / 0 - Off