Analog input
configuration
Current/Voltage input for
frequency reference input
Switch between current (I2) and voltage
(V2) input modes using SW4 on the IO TB
board.
I2 - Modify a frequency reference via
analog current input.
V2 - Modify a frequency reference via
analog voltage input.
Input current: 0–20 mA
Maximum Input: 24 mA
Input resistance 249 Ω
Frequency Reference
input via Pulse Train
Modify a frequency reference via Pulse
Train input from 0 to 32 kHz.
Low Level: 0–0.8 V, High Level: 3.5–12 V.
Outputs/Communication Terminal Labels and Descriptions
Switch between current (IO) and voltage (VO)
output modes using SW5 on the IO TB board.
IO - 4-20mA output representing various inverter
information. Set OUT-01 to output frequency, output
current, output voltage and others.
VO - 0-10VDC output.
Output Signal Specifications:
Output current: 0–20 mA
Maximum output current: 24 mA
Output voltage: 0–10 V
Maximum output voltage/current: 12 V/12 mA
Factory default 4-20mA OUT-01: Frequency
0-10VDC output representing various inverter
information. Set OUT-07 to output frequency, output
current, output voltage and others.
Output Signal Specifications:
Output voltage: 0–10 V
Maximum output voltage/current: 12 V/12 mA
Factory default 0-10V OUT-07: Frequency