43
890053-00-02
Installing the Inverter
Function
Label
Name
Description
Relay
Outputs
A1/C1/B1
Multi-function output
relay
(Form C)
Form C, configurable output terminal. Activates
based on OUT-31 setting.
Normal operation: B1-C1 closed. A1-C1 open
Activated condition: A1-C1 closed, B1-C1 open
Specifications:
N.O.: AC250 V, < 2 A, DC 30 V, < 3 A
N.C.: AC250 V, < 1 A, DC 30 V, < 1 A
Factory default: OUT-31: Trip
Relay
Outputs
A2/C2
A3/C3
A4/C4
A5/C5
Multi-function
output relays
(Form A)
Form A, configurable output terminals. Activate
based on OUT-32 ~ OUT-36 settings.
Specifications:
AC 250 V, < 5 A, DC 30 V, < 5 A.
Factory defaults:
OUT-32: Run
OUT-33~36: None
Digital
Output
Q1/(TO)
Multi-function (Open
Collector) / Pulse
Output
Open collector, configurable output terminal.
Activates based on OUT-36 setting. Use the “24”
terminal or external power source.
Can provide a pulsed output (Set OUT-36 = TO)
configurable to OUT-61 settings.
Specifications: DC 26 V, 50 mA or less
Pulsed output frequency: 032 kHz., 012 V
EG
Common
Ground terminal for Q1 (open collector).
24
24 VDC power
supply
Primary use is for supplying the digital input
terminals in PNP mode. May be used for other
purposes (EX: 2-wire transducer). Caution on the
limited power rating of the “24” terminal.
Specifications:
24VDC Maximum output current: 100 mA
RS-485
S+/S-/SG
RS-485 signal line
Send / receive RS-485 signals. Refer to 10, RS-485
Communication Features on page 299 for more
details.
Note
STP (Shielded Twisted Pair) cable has a highly conductive shielded screen around
twisted cable pairs. STP cables protect conductors from electromagnetic interference.
When making wiring connections at the control terminals ensure that the total cable length
does not exceed 165 ft (50 m).
Ensure that the length of any safety related wiring does not exceed 100 ft (30 m).
Ensure that the cable length between the keypad and the inverter does not exceed 50 ft
(15.24 m). Cable connections longer than 50 ft (15.24 m) may cause signal errors.
Use a ferrite core to protect signal cables from electro-magnetic interference.
When using cable ties on control wiring, apply the cable ties no closer than 6 inches from
the inverter. This provides sufficient access to fully close the terminal cover.