EasyManuals Logo

Danfoss VLT AutomationDrive Programming Guide

Danfoss VLT AutomationDrive
234 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #109 background imageLoading...
Page #109 background image
3.10 Parameters: 8-** Communications and
Options
3.10.1 8-0* General Settings
8-01 Control Site
Option: Function:
The setting in this parameter overrides
the settings in 8-50 Coasting Select to
8-56 Preset Reference Select.
[0] * Digital and
ctrl.word
Control by using both digital input and
control word.
[1] Digital only Control by using digital inputs only.
[2] Controlword only Control by using control word only.
8-02 Control Word Source
Select the source of the control word: one of two serial interfaces
or four installed options. During initial power-up, the Adjustable
frequency drive automatically sets this parameter to Option A [3]
if it detects a valid Serial communication bus option installed in
slot A. If the option is removed, the Adjustable frequency drive
detects a change in the configuration, sets 8-02 Control Word
Source back to default setting RS-485, and the Adjustable
frequency drive then trips. If an option is installed after initial
power-up, the setting of 8-02 Control Word Source will not
change but the Adjustable frequency drive will trip and display:
Alarm 67 Option Changed.
When you retrofit a bus option into a Adjustable frequency drive
that did not have a bus option installed to begin with, you must
take an ACTIVE decision to move the control to bus-based. This
is done for safety reasons in order to avoid an accidental change.
Option: Function:
[0] None
[1] FC RS485
[2] FC USB
[3] * Option A
[4] Option B
[5] Option C0
[6] Option C1
[30] External Can
NOTE!
This parameter cannot be adjusted while the motor is
running.
8-03 Control Word Timeout Time
Range: Function:
1.0 s* [Application
dependant]
Enter the maximum time expected to
pass between the reception of two
consecutive messages. If this time is
exceeded, it indicates that the serial
8-03 Control Word Timeout Time
Range: Function:
communication has stopped. The
function selected in 8-04 Control Word
Timeout Function will then be carried
out. The timeout counter is triggered by
a valid control word.
8-04 Control Word Timeout Function
Select the timeout function. The timeout function activates when
the control word fails to be updated within the time period
specified in 8-03 Control Word Timeout Time.
Option: Function:
[0] * Off Resumes control via serial bus (Serial
communication bus or standard) using the
most recent control word.
[1] Freeze output Freezes output frequency until communi-
cation resumes.
[2] Stop Stops with auto-restart when communi-
cation resumes.
[3] Jogging Runs the motor at JOG frequency until
communication resumes.
[4] Max. speed Runs the motor at maximum frequency
until communication resumes.
[5] Stop and trip Stops the motor, then resets the Adjustable
frequency drive in order to restart: via the
Serial communication bus, via the reset
button on the LCP or via a digital input.
[7] Select setup 1 Changes the set-up upon reestablishment of
communication following a control word
timeout. If communication resumes causing
the timeout situation to disappear,
8-05 End-of-Timeout Function defines
whether to resume the set-up used before
the timeout or to retain the set-up
endorsed by the timeout function.
[8] Select setup 2
See [7] Select setup 1
[9] Select setup 3
See [7] Select setup 1
[10] Select setup 4
See [7] Select setup 1
[26] Trip
NOTE!
The following configuration is required in order to change
the set-up after a timeout:
Set 0-10 Active Set-up to [9] Multi set-up and select the
relevant link in 0-12 This Set-up Linked to.
Parameter Descriptions FC 300 Programming Guide
3-84 MG33MD22 - VLT
®
is a registered Danfoss trademark
3
3
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx

Table of Contents

Other manuals for Danfoss VLT AutomationDrive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive and is the answer not in the manual?

Danfoss VLT AutomationDrive Specifications

General IconGeneral
Supply Voltage3 x 200-240 V ±10% 3 x 380-500 V ±10% 3 x 525-600 V ±10%
EnclosureIP20
Output Power Range0.25 kW - 1.5 MW
Communication ProtocolsModbus RTU
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short circuit, Ground fault, Motor overload
Ambient Temperature Range-10°C to +50°C (14°F to 122°F)

Related product manuals