EasyManuals Logo

Danfoss VLT AutomationDrive Programming Guide

Danfoss VLT AutomationDrive
234 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #117 background imageLoading...
Page #117 background image
8-55 Set-up Select
Option: Function:
[1] Bus Activates the set-up selection via the serial
communication port or serial communication
option.
[2] Logic
AND
Activates the set-up selection via the serial
communication bus/serial communication port,
AND additionally via one of the digital inputs.
[3] * Logic OR Activate the set-up selection via the serial
communication bus/serial communication port
OR via one of the digital inputs.
8-56 Preset Reference Select
Option: Function:
Select control of the Adjustable frequency drive
Preset Reference selection via the terminals
(digital input) and/or via the serial communi-
cation bus.
[0] Digital
input
Activates Preset Reference selection via a digital
input.
[1] Bus Activates Preset Reference selection via the
serial communication port or serial communi-
cation option.
[2] Logic AND Activates Preset Reference selection via the
serial communication bus/serial communication
port, AND additionally via one of the digital
inputs.
[3] * Logic OR Activates the Preset Reference selection via the
serial communication bus/serial communication
port OR via one of the digital inputs.
8-57 Profidrive OFF2 Select
Select control of the drive OFF2 selection via the terminals
(digital input) and/or via the serial communication bus. This
parameter is active only when par. 8-01 Control Site is set to [0]
Digital and ctrl. word and par. 8-10 is set to [1] Profidrive profile.
Option: Function:
[0] Digital input
[1] Bus
[2] Logic AND
[3] * Logic OR
8-58 Profidrive OFF3 Select
Select control of the drive OFF3 selection via the terminals
(digital input) and/or via the serial communication bus. This
parameter is active only when par. 8-01 Control Site is set to [0]
Digital and control word and par. 8-10 is set to [1] Profidrive
profile.
Option: Function:
[0] Digital input
[1] Bus
8-58 Profidrive OFF3 Select
Select control of the drive OFF3 selection via the terminals
(digital input) and/or via the serial communication bus. This
parameter is active only when par. 8-01 Control Site is set to [0]
Digital and control word and par. 8-10 is set to [1] Profidrive
profile.
Option: Function:
[2] Logic AND
[3] * Logic OR
3.10.6 8-8* AFD Port Diagnos.
These parameters are used for monitoring the bus
communication via the Adjustable Frequency Drive Port.
8-80 Bus Message Count
Range: Function:
0 * [0 - 0 ] This parameter shows the number of valid
messages detected on the bus.
8-81 Bus Error Count
Range: Function:
0 * [0 - 0 ] This parameter shows the number of messages
with faults (e.g., CRC fault), detected on the bus.
8-82 Slave Messages Rcvd
Range: Function:
0 * [0 - 0 ] This parameter shows the number of valid
messages addressed to the slave, sent by the
Adjustable frequency drive.
8-83 Slave Error Count
Range: Function:
0 * [0 - 0 ] This parameter shows the number of error
messages, which could not be executed by the
Adjustable frequency drive.
3.10.7 8-9* Bus Jog
8-90 Bus Jog 1 Speed
Range: Function:
100 RPM* [ 0 - par. 4-13
RPM]
Enter the jog speed. This is a fixed
jog speed activated via the serial
port or serial communication bus
option.
Parameter Descriptions FC 300 Programming Guide
3-92 MG33MD22 - VLT
®
is a registered Danfoss trademark
3
3
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx

Table of Contents

Other manuals for Danfoss VLT AutomationDrive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive and is the answer not in the manual?

Danfoss VLT AutomationDrive Specifications

General IconGeneral
Supply Voltage3 x 200-240 V ±10% 3 x 380-500 V ±10% 3 x 525-600 V ±10%
EnclosureIP20
Output Power Range0.25 kW - 1.5 MW
Communication ProtocolsModbus RTU
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short circuit, Ground fault, Motor overload
Ambient Temperature Range-10°C to +50°C (14°F to 122°F)

Related product manuals