EasyManuals Logo

Danfoss VLT AutomationDrive Programming Guide

Danfoss VLT AutomationDrive
234 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #52 background imageLoading...
Page #52 background image
3.3.10.5 Klixon
The Klixon type thermal circuit breaker uses a KLIXON
®
metal dish. At a predetermined overload, the heat caused
by the current through the disc causes a trip.
Using a digital input and 24 V as power supply:
Example: The Adjustable frequency drive trips when the
motor temperature is too high
Parameter set-up:
Set 1-90 Motor Thermal Protection to Thermistor Trip [2]
Set 1-93 Thermistor Source to Digital Input [6]
PTC / Thermistor
OFF
ON
+24V
12 13 18 3732
A
2719 29 33
B
20
GND
R<6.6 k Ω >10.8 k Ω
130BA151.11
1-91 Motor External Fan
Option: Function:
[0] * No No external fan is required, i.e., the motor is derated
at low speed.
[1] Yes Applies an external motor fan (external ventilation), so
that no derating of the motor is required at low
speed. The upper curve in graph above (fout = 1 x
fM,N) is followed if the motor current is lower than
nominal motor current (see 1-24 Motor Current). If the
motor current exceeds nominal current, the operation
time still decreases as if no fan were installed.
1-93 Thermistor Source
Option: Function:
Select the input to which the thermistor
(PTC sensor) should be connected. An
analog input option [1] or [2] cannot be
selected if the analog input is already in
use as a reference source (selected in
3-15 Reference 1 Source, 3-16 Reference 2
Source or 3-17 Reference 3 Source ).
When using MCB 112, choice [0] None
must always be selected.
[0] * None
[1] Analog input 53
[2] Analog input 54
[3] Digital input 18
[4] Digital input 19
[5] Digital input 32
[6] Digital input 33
NOTE!
This parameter cannot be adjusted while the motor is
running.
NOTE!
Digital input should be set to [0] PNP - Active at 24V in
5-00 Digital I/O Mode.
1-94 ATEX ETR cur.lim. speed reduction
FC 302 only.
Only visible if 1-90 Motor Thermal Protection is set to [20].
Range: Function:
0.0 %* [0.0 - 100.0 %]
The reaction for operating in Ex-e current limit must be
configured.
0%: The Adjustable frequency drive does not change
anything besides issuing warning 163 ATEX ETR
cur.lim.warning.
>0%: The Adjustable frequency drive issuing warning 163
and reduces motor speed following ramp 2 (parameter
group 3-5*).
Example:
Actual reference = 50 RPM
1-94 ATEX ETR cur.lim. speed reduction = 20%
Resulting reference = 40 RPM
1-95 KTY Sensor Type
Option: Function:
Select the used type of KTY sensor. FC 302
only.
[0] * KTY Sensor 1 1kΩ at 212° F [100° C]
[1] KTY Sensor 2 1kΩ at 77 °F [25 °C]
[2] KTY Sensor 3 2kΩ at 77 °F [25 °C]
1-96 KTY Thermistor Resource
Option: Function:
Selecting analog input terminal 54 to be used
as KTY sensor input. Terminal 54 cannot be
selected as KTY source if otherwise used as
reference (see 3-15 Reference Resource 1 to
3-17 Reference Resource 3).
FC 302 only.
NOTE!
Connection of KTY sensor between term.
54 and 55 (GND). See picture in section
KTY Sensor Connection.
[0] * None
Parameter Descriptions FC 300 Programming Guide
MG33MD22 - VLT
®
is a registered Danfoss trademark 3-27
3
3
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx

Table of Contents

Other manuals for Danfoss VLT AutomationDrive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive and is the answer not in the manual?

Danfoss VLT AutomationDrive Specifications

General IconGeneral
Supply Voltage3 x 200-240 V ±10% 3 x 380-500 V ±10% 3 x 525-600 V ±10%
EnclosureIP20
Output Power Range0.25 kW - 1.5 MW
Communication ProtocolsModbus RTU
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short circuit, Ground fault, Motor overload
Ambient Temperature Range-10°C to +50°C (14°F to 122°F)

Related product manuals