9-65 Profile Number
Range: Function:
0 * [0 - 0 ] This parameter contains the profile identification.
Byte 1 contains the profile number and byte 2 the
version number of the profile.
NOTE!
This parameter is not visible via LCP.
9-67 Control Word 1
Range: Function:
0* [0 - 65535 ] This parameter accepts the control word from
a Master Class 2 in the same format as PCD 1.
9-68 Status Word 1
Range: Function:
0* [0 - 65535 ] This parameter delivers the status word for a
Master Class 2 in the same format as PCD 2.
9-70 Programming Set-up
Option: Function:
Select the set-up to be edited.
[0] Factory setup Uses default data. This option can be used
as a data source to return the other set-ups
to a known state.
[1] Set-up 1 Edits Set-up 1.
[2] Set-up 2 Edits Set-up 2.
[3] Set-up 3 Edits Set-up 3.
[4] Set-up 4 Edits Set-up 4.
[9] * Active Set-up Follows the active set-up selected in
0-10 Active Set-up.
This parameter is unique to LCP and serial communication
busses. See also 0-11 Programming Set-up.
9-71 Profibus Save Data Values
Option: Function:
Parameter values changed via Profibus are not
automatically stored in non-volatile memory.
Use this parameter to activate a function that
stores parameter values in the EEPROM non-
volatile memory, so changed parameter values
will be retained at power-down.
[0] * Off Deactivates the non-volatile storage function.
[1] Store all
setups
Stores all parameter values for all set-ups in the
non-volatile memory. The selection returns to
Off [0] when all parameter values have been
stored.
9-71 Profibus Save Data Values
Option: Function:
[2] Store all
setups
Stores all parameter values for all set-ups in the
non-volatile memory. The selection returns to
Off [0] when all parameter values have been
stored.
9-72 ProfibusDriveReset
Option: Function:
[0] * No action
[1] Power-on
reset
Resets Adjustable frequency drive upon
power-up, as for power-cycle.
[3] Comm
option reset
Resets the Profibus option only, useful after
changing certain settings in parameter
group 9-**, e.g., 9-18 Node Address.
When reset, the Adjustable frequency drive
disappears from the serial communication
bus, which may cause a communication
error from the master.
9-75 DO Identification
Range: Function:
0* [0 - 65535 ] Provides information about the DO (Drive
Object).
9-80 Defined Parameters (1)
Array [116]
No LCP access
Read only
Range: Function:
0 * [0 - 9999 ] This parameter displays a list of all the defined
Adjustable frequency drive parameters available
for Profibus.
9-81 Defined Parameters (2)
Array [116]
No LCP access
Read only
Range: Function:
0 * [0 - 9999 ] This parameter displays a list of all the defined
Adjustable frequency drive parameters available
for Profibus.
9-82 Defined Parameters (3)
Array [116]
No LCP access
Read only
Range: Function:
0 * [0 - 9999 ] This parameter displays a list of all the defined
Adjustable frequency drive parameters available
for Profibus.
Parameter Descriptions FC 300 Programming Guide
MG33MD22 - VLT
®
is a registered Danfoss trademark 3-99
3
3
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx

Table of Contents

Other manuals for Danfoss VLT AutomationDrive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive and is the answer not in the manual?

Danfoss VLT AutomationDrive Specifications

General IconGeneral
Supply Voltage3 x 200-240 V ±10% 3 x 380-500 V ±10% 3 x 525-600 V ±10%
EnclosureIP20
Output Power Range0.25 kW - 1.5 MW
Communication ProtocolsModbus RTU
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short circuit, Ground fault, Motor overload
Ambient Temperature Range-10°C to +50°C (14°F to 122°F)