EasyManuals Logo
Home>Danfoss>DC Drives>VLT AutomationDrive

Danfoss VLT AutomationDrive Programming Guide

Danfoss VLT AutomationDrive
234 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #53 background imageLoading...
Page #53 background image
1-96 KTY Thermistor Resource
Option: Function:
[2] Analog
input 54
1-97 KTY Threshold level
Range: Function:
80 C* [-40 - 140 C]
1-98 ATEX ETR interpol. points freq.
FC 302 only.
Only visible if 1-90 Motor Thermal Protection is set to [20].
Range: Function:
Application
dependent*
[Application
dependant]
Definition of
thermal limitation
curve.
Enter the four frequency points [Hz] from the motor
nameplate into this array. Together with 1-99 ATEX ETR
interpol points current, these make up a table (f [Hz],I [%]).
NOTE!
All frequency/current limit points from the motor
nameplate or motor data sheet must be programmed.
1 0 0 %
8 0 %
4 0 %
5 Hz 15 Hz 25 Hz 50 Hz
130BB909.10
Figure 3.7 Example of ATEX ETR thermal limitation curve.
x-axis: f
m
[Hz]
y-axis: I
m
/I
m,n
x 100 [%]
1-98 ATEX ETR interpol. points freq. 1-99 ATEX ETR interpol points
current
[0] = 5 Hz [0] = 40%
[1] = 15 Hz [1] = 80%
[2] = 25 Hz [2] = 100%
[3] = 50 Hz [3] = 100%
All operating points underneath the curve are allowed
continuously. Above the line, however, only for a limited
time calculated as a function of the overload. In the event
of a machine current greater than 1.5 times the rated
current, shut down is immediate.
1-99 ATEX ETR interpol points current
FC 302 only.
Only visible if 1-90 Motor Thermal Protection is set to [20] or [21].
Range: Function:
Application
dependent*
[0 - 100 %] Definition of thermal
limitation curve. For
example, see 1-98 ATEX
ETR interpol. points freq.
Use the four current points [A] from the motor nameplate.
Calculate the values as percentage of nominal motor
current, I
m
/I
m,n
x 100 [%], and enter into this array.
Together with 1-98 ATEX ETR interpol. points freq., these
make up a table (f [Hz],I [%]).
NOTE!
All frequency/current limit points from the motor
nameplate or motor data sheet must be programmed.
Parameter Descriptions FC 300 Programming Guide
3-28 MG33MD22 - VLT
®
is a registered Danfoss trademark
3
3
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx

Table of Contents

Other manuals for Danfoss VLT AutomationDrive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive and is the answer not in the manual?

Danfoss VLT AutomationDrive Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive
CategoryDC Drives
LanguageEnglish

Related product manuals