3.16 Parameters: 15-** Drive Information
3.16.1 15-0* Operating Data
15-00 Operating Hours
Range: Function:
0 h* [0 - 2147483647 h] View how many hours the Adjustable
frequency drive has run. The value is
saved when the Adjustable frequency
drive is turned off.
15-01 Running Hours
Range: Function:
0 h* [0 - 2147483647
h]
View how many hours the motor has
run. Reset the counter in 15-07 Reset
Running Hours Counter. The value is
saved when the Adjustable frequency
drive is turned off.
15-02 kWh Counter
Range: Function:
0 kWh* [0 - 2147483647
kWh]
Registering the power consumption
of the motor as a mean value over
one hour. Reset the counter in
15-06 Reset kWh Counter.
15-03 Power Up's
Range: Function:
0 * [0 - 2147483647 ] View the number of times the
Adjustable frequency drive has been
powered up.
15-04 Over Temp's
Range: Function:
0 * [0 - 65535 ] View the number of Adjustable frequency
drive temperature faults which have occurred.
15-05 Over Volt's
Range: Function:
0 * [0 - 65535 ] View the number of Adjustable frequency
drive overvoltages which have occurred.
15-06 Reset kWh Counter
Option: Function:
[0] * Do not reset
Select Do not reset [0] if no reset of the kWh
counter is desired.
[1] Reset counter
Select Reset [1] and press [OK] to reset the
kWh counter to zero (see 15-02 kWh
Counter).
NOTE!
The reset is carried out by pressing [OK].
15-07 Reset Running Hours Counter
Option: Function:
[0] * Do not reset
[1] Reset counter
Select Reset [1] and press [OK] to reset the
Running Hours counter to zero (see
15-01 Running Hours). This parameter cannot
be selected via the serial port, RS-485.
Select Do not reset [0] if no reset of the
Running Hours counter is desired.
3.16.2 15-1* Data Log Settings
The Data Log enables continuous logging of up to 4 data
sources (15-10 Logging Source) at individual rates
(15-11 Logging Interval). A trigger event (15-12 Trigger
Event) and window (15-14 Samples Before Trigger) are used
to start and stop the logging conditionally.
15-10 Logging Source
Array [4]
Option: Function:
Select which variables are to be
logged.
[0] * None
[15] Readout: actual setup
[1472] Legacy Alarm Word
[1473] Legacy Warning Word
[1474] Leg. Ext. Status Word
[1600] Control Word
[1601] Reference [Unit]
[1602] Reference %
[1603] Status Word
[1610] Power [kW]
[1611] Power [hp]
[1612] Motor Voltage
[1613] Frequency
[1614] Motor Current
[1616] Torque [Nm]
[1617] Speed [RPM]
[1618] Motor Thermal
[1621] Torque [%] High Res.
[1622] Torque [%]
[1625] Torque [Nm] High
[1630] DC Link Voltage
[1632] Brake Energy /s
[1633] Brake Energy /2 min
[1634] Heatsink Temp.
[1635] Inverter Thermal
Parameter Descriptions FC 300 Programming Guide
3-136 MG33MD22 - VLT
®
is a registered Danfoss trademark
3
3
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx

Table of Contents

Other manuals for Danfoss VLT AutomationDrive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive and is the answer not in the manual?

Danfoss VLT AutomationDrive Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive
CategoryDC Drives
LanguageEnglish

Related product manuals