EasyManuals Logo

Danfoss VLT AutomationDrive Programming Guide

Danfoss VLT AutomationDrive
234 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #84 background imageLoading...
Page #84 background image
5-33 Term X30/7 Digi Out (MCB 101)
Option: Function:
[61] Comparator 1
[62] Comparator 2
[63] Comparator 3
[64] Comparator 4
[65] Comparator 5
[70] Logic rule 0
[71] Logic rule 1
[72] Logic rule 2
[73] Logic rule 3
[74] Logic rule 4
[75] Logic rule 5
[80] SL digital output A
[81] SL digital output B
[82] SL digital output C
[83] SL digital output D
[84] SL digital output E
[85] SL digital output F
[120] Local ref active
[121] Remote ref active
[122] No alarm
[123] Start command activ
[124] Running reverse
[125] Drive in hand mode
[126] Drive in auto mode
[151] ATEX ETR cur. alarm
[152] ATEX ETR freq. alarm
[153] ATEX ETR cur. warning
[154] ATEX ETR freq. warning
[189] External Fan Control
[190] Safe Function active
[191] Safe Opt. Reset req.
[192] RS Flipflop 0
[193] RS Flipflop 1
[194] RS Flipflop 2
[195] RS Flipflop 3
[196] RS Flipflop 4
[197] RS Flipflop 5
[198] RS Flipflop 6
[199] RS Flipflop 7
3.7.4 5-4* Relays
Parameters for configuring the timing and the output
functions for the relays.
5-40 Function Relay
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB
113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6]
(MCB 105), Relay 8 [7] (MCB 105), Relay 9 [8] (MCB 105))
Option: Function:
[0] * No operation All digital and relay outputs are
default set to “No Operation”.
[1] Control ready The control card is ready. For
example, Feedback from a drive
where the control is supplied by an
external 24 V (MCB 107) and the
main power to drive is not detected.
[2] Drive ready Drive is ready to operate. Line power
and control supplies are OK.
[3] Drive rdy/rem ctrl The Adjustable frequency drive is
ready for operation and is in auto on
mode
[4] Enable / no warning Ready for operation. No start or stop
commands have been applied (start/
disable). No warnings are active.
[5] Running Motor is running, and shaft torque
present.
[6] Running / no
warning
Output speed is higher than the
speed set in 1-81 Min Speed for
Function at Stop [RPM] Min Speed for
Function at Stop [RPM]. The motor is
running and no warnings.
[7] Run in range/no
warn
Motor is running within the
programmed current and speed
ranges set in 4-50 Warning Current
Low and 4-53 Warning Speed High.
No warnings.
[8] Run on ref/no warn Motor runs at reference speed. No
warnings.
[9] Alarm An alarm activates the output. No
warnings
[10] Alarm or warning An alarm or a warning activates the
output.
[11] At torque limit
The torque limit set in 4-16 Torque
Limit Motor Mode or 4-17 Torque
Limit Generator Mode has been
exceeded.
[12] Out of current
range
The motor current is outside the
range set in 4-18 Current Limit.
[13] Below current, low
Motor current is lower than set in
4-50 Warning Current Low.
Parameter Descriptions FC 300 Programming Guide
MG33MD22 - VLT
®
is a registered Danfoss trademark 3-59
3
3
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx

Table of Contents

Other manuals for Danfoss VLT AutomationDrive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive and is the answer not in the manual?

Danfoss VLT AutomationDrive Specifications

General IconGeneral
Supply Voltage3 x 200-240 V ±10% 3 x 380-500 V ±10% 3 x 525-600 V ±10%
EnclosureIP20
Output Power Range0.25 kW - 1.5 MW
Communication ProtocolsModbus RTU
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short circuit, Ground fault, Motor overload
Ambient Temperature Range-10°C to +50°C (14°F to 122°F)

Related product manuals