EasyManuals Logo

Danfoss VLT AutomationDrive Programming Guide

Danfoss VLT AutomationDrive
234 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #47 background imageLoading...
Page #47 background image
1-73 Flying Start
Option: Function:
This function makes it possible to catch
a motor that is spinning freely due to a
line drop-out.
[0] * Disabled No function
[1] Enabled Enables the Adjustable frequency drive
to “catch” and control a spinning motor.
When 1-73 Flying Start is enabled,
1-71 Start Delay and 1-72 Start Function
have no function.
[2] Enabled Always
[3] Enabled Ref. Dir.
[4] Enab. Always
Ref. Dir.
NOTE!
This parameter cannot be adjusted while motor is running.
NOTE!
This function is not recommended for hoisting
applications.
For power levels above 75 hp [55 kW], flux mode must be
used to achieve the best performance.
NOTE!
To obtain the best flying start performance the advanced
motor data, parameters 1-30 through 1-35, must be
correct.
1-74 Start Speed [RPM]
Range: Function:
Application
dependent*
[0 - 600 RPM] This parameter can be used
for hoist applications (cone
rotor).
1-75 Start Speed [Hz]
Range: Function:
Application
dependent*
[Application
dependant]
This parameter can be used for
hoist applications (cone rotor).
Set a motor start speed. After the
start signal, the output speed
leaps to set value. Set the start
function in 1-72 Start Function to
[3], [4] or [5], and set a start
delay time in 1-71 Start Delay.
1-76 Start Current
Range: Function:
0.00
A*
[Application
dependant]
Some motors, e.g., cone rotor motors,
need extra current/starting speed to
1-76 Start Current
Range: Function:
disengage the rotor. To obtain this
boost, set the required current in
1-76 Start Current. Set 1-74 Start Speed
[RPM]. Set 1-72 Start Function to [3] or
[4], and set a start delay time in
1-71 Start Delay.
This parameter can be used for hoist
applications (cone rotor).
3.3.8 1-8* Stop Adjustments
1-80 Function at Stop
Option: Function:
Select the Adjustable frequency drive
function after a stop command or after the
speed is ramped down to the settings in
1-81 Min Speed for Function at Stop [RPM].
[0]
*
Coast Leaves motor in free mode. The motor is
disconnected from the Adjustable frequency
drive.
[1] DC hold Energizes motor with a DC holding current
(see 2-00 DC Hold Current).
[2] Motor check Checks if a motor has been connected.
[3] Pre-
magnetizing
Builds up a magnetic field while the motor
is stopped. This allows the motor to
produce torque quickly at subsequent start
commands (asynchronous motors only). This
pre-magnetizing function does not help the
very first start command. Two different
solutions are available to pre-magnetize the
machine for the first start command:
1. Start the Adjustable frequency
drive with a 0RPM reference and
wait 2 to 4 rotor time constants
(see below) before increasing the
speed reference.
2a. Set 1-71 Start Delay to the
desired pre-mag time (2 to 4 rotor
time constants - see below).
2b. Set 1-72 to either [0] DC-hold
or [1] DC Brake.
Set the DC hold or DC brake
current magnitude (2-00 or 2-01) to
be equal to I_pre-mag = Unom /
(1.73 x Xh)
Sample rotor time constants =
(Xh+X2) / (6.3*Freq_nom*Rr)
Parameter Descriptions FC 300 Programming Guide
3-22 MG33MD22 - VLT
®
is a registered Danfoss trademark
3
3
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx

Table of Contents

Other manuals for Danfoss VLT AutomationDrive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive and is the answer not in the manual?

Danfoss VLT AutomationDrive Specifications

General IconGeneral
Supply Voltage3 x 200-240 V ±10% 3 x 380-500 V ±10% 3 x 525-600 V ±10%
EnclosureIP20
Output Power Range0.25 kW - 1.5 MW
Communication ProtocolsModbus RTU
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short circuit, Ground fault, Motor overload
Ambient Temperature Range-10°C to +50°C (14°F to 122°F)

Related product manuals