EasyManuals Logo

Danfoss VLT AutomationDrive Programming Guide

Danfoss VLT AutomationDrive
234 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #170 background imageLoading...
Page #170 background image
16-71 Relay Output [bin]
Range: Function:
0 * [0 - 511 ] View the settings of all relays.
16-72 Counter A
Range: Function:
0* [-2147483648 -
2147483647 ]
View the present value of Counter A.
Counters are useful as comparator
operands, see 13-10 Comparator Operand.
The value can be reset or changed either
via digital inputs (parameter group 5-1*) or
by using an SLC action (13-52 SL Controller
Action).
16-73 Counter B
Range: Function:
0* [-2147483648 -
2147483647 ]
View the present value of Counter B.
Counters are useful as comparator
operands (13-10 Comparator Operand).
The value can be reset or changed either
via digital inputs (parameter group 5-1*) or
by using an SLC action (13-52 SL Controller
Action).
16-74 Prec. Stop Counter
Range: Function:
0* [0 - 2147483647 ] Returns the actual counter value of
precise counter (1-84 Precise Stop Counter
Value).
16-75 Analog In X30/11
Range: Function:
0.000 * [-20.000 - 20.000 ] View the actual value at input
X30/11 of MCB 101.
16-76 Analog In X30/12
Range: Function:
0.000 * [-20.000 - 20.000 ] View the actual value at input
X30/12 of MCB 101.
16-77 Analog Out X30/8 [mA]
Range: Function:
0.000 * [0.000 - 30.000 ] View the actual value at input X30/8
in mA.
16-78 Analog Out X45/1 [mA]
Range: Function:
0.000* [0.000 - 30.000 ] View the actual value at output X45/1.
The value shown reflects the selection
in 6-70 Terminal X45/1 Output.
16-79 Analog Out X45/3 [mA]
Range: Function:
0.000* [0.000 - 30.000 ] View the actual value at output X45/3.
The value shown reflects the selection
in 6-80 Terminal X45/3 Output.
3.17.5 16-8* Serial communication bus &
FC Port
Parameters for reporting the BUS references and control
words.
16-80 Fieldbus CTW 1
Range: Function:
0 * [0 -
65535 ]
View the two-byte control word (CTW) received
from the bus master. Interpretation of the
control word depends on the Serial
communication bus option installed and the
control word profile selected in 8-10 Control
Profile.
For more information, please refer to the
relevant Serial communication bus manual.
16-82 Fieldbus REF 1
Range: Function:
0 * [-200 -
200 ]
View the two-byte word sent with the control
word form the bus master to set the reference
value.
For more information, refer to the relevant
serial communication bus manual.
16-84 Comm. Option STW
Range: Function:
0 * [0 - 65535 ] View the extended Serial communication bus
comm. option status word.
For more information, please refer to the
relevant Serial communication bus manual.
Parameter Descriptions FC 300 Programming Guide
MG33MD22 - VLT
®
is a registered Danfoss trademark 3-145
3
3
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx

Table of Contents

Other manuals for Danfoss VLT AutomationDrive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive and is the answer not in the manual?

Danfoss VLT AutomationDrive Specifications

General IconGeneral
Supply Voltage3 x 200-240 V ±10% 3 x 380-500 V ±10% 3 x 525-600 V ±10%
EnclosureIP20
Output Power Range0.25 kW - 1.5 MW
Communication ProtocolsModbus RTU
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short circuit, Ground fault, Motor overload
Ambient Temperature Range-10°C to +50°C (14°F to 122°F)

Related product manuals