NOTE!
When Auto Reset/Warning is selected the Adjustable
frequency drive opens up for automatic restart.
Overview of functions, alarms and warnings
Function No. PTC Relay
No Function [0] - -
Safe Stop Alarm [1]* - Safe Stop [A68]
Safe Stop Warning [3] - Safe Stop [W68]
PTC 1 Alarm [4] PTC 1 Safe Stop
[A71]
-
PTC 1 Warning [5] PTC 1 Safe Stop
[W71]
-
PTC 1 & Relay A [6] PTC 1 Safe Stop
[A71]
Safe Stop [A68]
PTC 1 & Relay W [7] PTC 1 Safe Stop
[W71]
Safe Stop [W68]
PTC 1 & Relay A/W [8] PTC 1 Safe Stop
[A71]
Safe Stop [W68]
PTC 1 & Relay W/A [9] PTC 1 Safe Stop
[W71]
Safe Stop [A68]
W means warning, and A means alarm. For further information, see
Alarms and Warnings in section Troubleshooting in the Design Guide
or in the Instruction Manual.
A dangerous failure related to the safe stop will give alarm:
Dangerous Failure [A72].
Please refer to in .
5-20 Terminal X46/1 Digital Input
Option: Function:
[0] * No operation This parameter is active when option module
MCB 113 is installed in the Adjustable
frequency drive. Functions are described
under 5-1* Digital Inputs
5-21 Terminal X46/3 Digital Input
Option: Function:
[0] * No operation This parameter is active when option
moduleMCB 113 is installed in the Adjustable
frequency drive. Functions are described
under 5-1* Digital Inputs
5-22 Terminal X46/5 Digital Input
Option: Function:
[0] * No operation This parameter is active when option
moduleMCB 113 is installed in the Adjustable
frequency drive. Functions are described
under 5-1* Digital Inputs
5-23 Terminal X46/7 Digital Input
Option: Function:
[0] * No operation This parameter is active when option
moduleMCB 113 is installed in the Adjustable
frequency drive. Functions are described
under 5-1* Digital Inputs
5-24 Terminal X46/9 Digital Input
Option: Function:
[0] * No operation This parameter is active when option module
MCB 113 is installed in the Adjustable
frequency drive. Functions are described
under 5-1* Digital Inputs
5-25 Terminal X46/11 Digital Input
Option: Function:
[0] * No operation This parameter is active when option
moduleMCB 113 is installed in the Adjustable
frequency drive. Functions are described
under 5-1* Digital Inputs
5-26 Terminal X46/13 Digital Input
Option: Function:
[0] * No operation This parameter is active when option module
MCB 113 is installed in the Adjustable
frequency drive. Functions are described
under 5-1* Digital Inputs
3.7.3 5-3* Digital Outputs
The 2 solid-state digital outputs are common for terminals
27 and 29. Set the I/O function for terminal 27 in
5-01 Terminal 27 Mode, and set the I/O function for
terminal 29 in 5-02 Terminal 29 Mode.
NOTE!
These parameters cannot be adjusted while the motor is
running.
[0] No operation
Default for all digital outputs and relay
outputs
[1] Control ready The control card is ready. For example,
Feedback from a Adjustable frequency
drive where the control is supplied by an
external 24 V (MCB 107) and the main
power to the unit is not detected.
[2] Drive ready The Adjustable frequency drive is ready
for operation and applies a supply signal
on the control board.
[3] Drive ready /
remote control
The Adjustable frequency drive is ready
for operation and is in [Auto on] mode.
Parameter Descriptions FC 300 Programming Guide
3-54 MG33MD22 - VLT
®
is a registered Danfoss trademark
3
3
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx

Table of Contents

Other manuals for Danfoss VLT AutomationDrive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive and is the answer not in the manual?

Danfoss VLT AutomationDrive Specifications

General IconGeneral
Supply Voltage3 x 200-240 V ±10% 3 x 380-500 V ±10% 3 x 525-600 V ±10%
EnclosureIP20
Output Power Range0.25 kW - 1.5 MW
Communication ProtocolsModbus RTU
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short circuit, Ground fault, Motor overload
Ambient Temperature Range-10°C to +50°C (14°F to 122°F)

Related product manuals