EasyManuals Logo

Danfoss VLT AutomationDrive Programming Guide

Danfoss VLT AutomationDrive
234 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #80 background image
[4] Enable / no
warning
Ready for operation. No start or stop
command is been given (start/disable).
No warnings are active.
[5] VLT running Motor is running and shaft torque is
present.
[6] Running / no
warning
Output speed is higher than the speed
set in 1-81 Min Speed for Function at Stop
[RPM]. The motor is running and there are
no warnings.
[7] Run in
range/no
warning
Motor is running within the programmed
current and speed ranges set in
4-50 Warning Current Low to 4-53 Warning
Speed High. There are no warnings.
[8] Run on
reference / no
warning
Motor runs at reference speed. No
warnings.
[9] Alarm An alarm activates the output. There are
no warnings.
[10] Alarm or
warning
An alarm or a warning activates the
output.
[11] At torque limit
The torque limit set in 4-16 Torque Limit
Motor Mode or 4-17 Torque Limit Generator
Mode has been exceeded.
[12] Out of current
range
The motor current is outside the range
set in 4-18 Current Limit.
[13] Below current,
low
Motor current is lower than set in
4-50 Warning Current Low.
[14] Above current,
high
Motor current is higher than set in
4-51 Warning Current High.
[15] Out of speed
range
Output frequency is outside the
frequency ranges set in 4-52 Warning
Speed Low and 4-53 Warning Speed High.
[16] Below speed,
low
Output speed is lower than the setting in
4-52 Warning Speed Low.
[17] Above speed,
high
Output speed is higher than the setting
in 4-53 Warning Speed High.
[18] Out of
feedback range
Feedback is outside the range set in
4-56 Warning Feedback Low and
4-57 Warning Feedback High.
[19] Below
feedback low
Feedback is below the limit set in
4-56 Warning Feedback Low.
[20] Above
feedback high
Feedback is above the limit set in
4-57 Warning Feedback High.
[21] Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the Adjustable frequency drive,
the brake resistor, or the thermistor.
[22] Ready, no
thermal
warning
Adjustable frequency drive is ready for
operation and there is no over-
temperature warning.
[23] Remote, ready,
no thermal
warning
Adjustable frequency drive is ready for
operation and is in [Auto on] mode.
There is no over-temperature warning.
[24] Ready, voltage
OK
Adjustable frequency drive is ready for
operation and the AC line voltage is
within the specified voltage range (see
General Specifications section in the
Design Guide).
[25] Reverse
Reversing. Logic ‘1’ when CW rotation of
the motor. Logic ‘0’ when CCW rotation
of the motor. If the motor is not rotating,
the output will follow the reference.
[26] Bus OK Active communication (no timeout) via
the serial communication port.
[27] Torque limit
and stop
Use in performing a coasting stop and in
torque limit condition. If the Adjustable
frequency drive has received a stop signal
and is at the torque limit, the signal is
Logic ‘0’.
[28] Brake, no brake
warning
Brake is active and there are no warnings.
[29] Brake ready, no
fault
Brake is ready for operation and there are
no faults.
[30] Brake fault
(IGBT)
Output is Logic ‘1’ when the brake IGBT is
short-circuited. Use this function to
protect the Adjustable frequency drive if
there is a fault on the brake modules. Use
the output/relay to cut out the AC line
voltage from the Adjustable frequency
drive.
[31] Relay 123 The relay is activated when Control Word
[0] is selected in parameter group 8-**.
[32] Mechanical
brake control
Enables control of an external mechanical
brake, see description in the section
Control of Mechanical Brake, and
parameter group 2-2*
[33] Safe stop
activated (FC
302 only)
Indicates that the safe stop on terminal
37 has been activated.
[40] Out of ref
range
Active when the actual speed is outside
settings in 4-52 Warning Speed Low to
4-55 Warning Reference High.
[41] Below
reference low
Active when actual speed is below speed
reference setting.
[42] Above
reference high
Active when actual speed is above speed
reference setting
[43] Extended PID
Limit
[45] Bus Ctrl Controls output via bus. The state of the
output is set in 5-90 Digital & Relay Bus
Control. The output state is retained in
the event of bus timeout.
[46] Bus Ctrl On at
timeout
Controls output via bus. The state of the
output is set in 5-90 Digital & Relay Bus
Control. In the event of a bus timeout,
the output state is set high (On).
Parameter Descriptions FC 300 Programming Guide
MG33MD22 - VLT
®
is a registered Danfoss trademark 3-55
3
3
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx

Table of Contents

Other manuals for Danfoss VLT AutomationDrive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive and is the answer not in the manual?

Danfoss VLT AutomationDrive Specifications

General IconGeneral
Supply Voltage3 x 200-240 V ±10% 3 x 380-500 V ±10% 3 x 525-600 V ±10%
EnclosureIP20
Output Power Range0.25 kW - 1.5 MW
Communication ProtocolsModbus RTU
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short circuit, Ground fault, Motor overload
Ambient Temperature Range-10°C to +50°C (14°F to 122°F)

Related product manuals