81901A “MSW_GPC-40/600A”_03-2021_ENG_page 103
3.23.3. Enabling manual power correction and storage
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea-
surement
Default
Single-
node
Multi-
node
Description
1042 18 16 bit 07.01.01 SP.r Global
MainMenu → Global → Controls → SP.r
R/W
■
Unsigned
Short
0
The parameter enables manual power correction and storage.
Options: 0 = No function
8 = Manual power correction based on mains voltage
32 = Disabling of local manual power storage (the last stored value is retrieved when switching off)
3.24. Start modes
3.24.1. Start mode at Power-On
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea-
surement
Default
Single-
node
Multi-
node
Description
1723
699 16 bit
07.02.09
P.Ont
M
MainMenu → M → Controls → P.Ont_1
R/W
■
Unsigned
Short
02747 07.03.09 E1
MainMenu → E1 → Controls → P.Ont_2
4795 01.04.09 E2
MainMenu → E2 → Controls → P.Ont_3
This parameter sets the mode in which the Advanced Power Controller starts up when power is supplied.
The mode is identified by an index.
Options:
Index Start modes
0 Operation of the controller resumes with the same
modalities as the last state prior to shutdown. Digital
input states always take priority over other states.
1 Software shutdown.
2 Software startup.