3.29. Delay Triggering
Delay Triggering is a function that inserts a trigger delay on
the first cycle with inductive loads in start modes ZC and
BF. The startup delay is expressed in degrees and can be
set in the dL.t parameter.
3.29.1. Delay triggering
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea-
surement
Default
Single-
node
Multi-
node
Description
1732
708 16 bit
09.01.08
dL.t
M
MainMenu M Power controls
dL.t_1
R/W
Unsigned
Short
de-
grees
see
table
2756 09.02.08 E1
MainMenu E1 Power controls
dL.t_2
4804 09.03.08 E2
MainMenu E2 Power controls
dL.t_3
The parameter sets the trigger delay, expressed in sexagesimal degrees (base 60), on the first cycle. The default value of the parameter
depends on the configuration:
Type of load
Default
GPC-M GPC-E1 GPC-E2
Three-phase star load without neutral or closed delta,
with DIP switch 5 = ON (inductive load)
40 40 90
All other types of load 60 60 60
min...max: 0...90
3.29.2. Delay triggering with rotation of phases 1-3-2
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea-
surement
Default
Single-
node
Multi-
node
Description
1796
772 16 bit
09.01.09
dL.tr
M
MainMenu M Power controls
dL.tr_1
R/W
Unsigned
Short
de-
grees
see
table
2820 09.02.09 E1
MainMenu E1 Power controls
dL.tr_2
4868 09.03.09 E2
MainMenu E2 Power controls
dL.tr_3
The parameter sets the trigger delay, expressed in sexagesimal degrees, with rotation of phases 1-3-2. The default value of the parameter
depends on the configuration:
Type of load
Default
GPC-M GPC-E1 GPC-E2
Three-phase star load without neutral or closed delta,
with DIP switch 5 = ON (inductive load)
90 90 40
All other types of load 60 60 60
min...max: 0...90