To shelve an alarm or alert for a specified time and/or reason
1. Call up the Alarm Summary or Alert Summary.
2. Right-click on the alarm or alert you want to shelve, and choose the Shelve Alarm or
Shelve Alert command.
The Shelve Alarm or Shelve Alert dialog box appears.
3. In the Reason for shelving list, select the reason for shelving the alarm or alert.
4. If you do not want to use the default shelving period, in the Shelving period list, select
a shelving period.
5. If you want to automatically unshelve the alarm or alert if it returns to normal, select the
Unshelve if the alarm returns to normal or the Unshelve if the alert returns to nor-
mal check box.
a. Enter the number of seconds (maximum 65,535 seconds, or 18:12:15 hrs) in the
Unshelve delay on return to normal box to specify the amount of time after which
the alarm or alert will be unshelved, once it returns to normal.
This helps to prevent nuisance alarms or alerts cluttering the display. See the topic
titled "Considerations for configuring an alarm unshelving delay" for more
information.
6. If appropriate for the alarm or alert, in the Comments box, type your detailed reason
for shelving the alarm or alert.
7. Click OK.
To unshelve an alarm or alert
1. Call up the Alarm or Alert Summary.
2. Select the (shelved alarms)/(shelved alerts) view.
3. Select the alarm or alert you want to unshelve.
4. Click the Unshelve Alarm or the Unshelve Alert button.
Considerations for configuring an alarm unshelving delay
Overview
There may be times when distracting or nuisance alarms are cluttering your display and you
choose to shelve an alarm for a specified period. If that alarm returns to normal at any time
during the shelving period, the alarm is unshelved. New alarms for the same point would
appear on the Alarm Summary. This is usual behavior for alarm shelving.
Responding to alarms
Honeywell 2017 135

Table of Contents

Other manuals for Honeywell Experion LX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Experion LX and is the answer not in the manual?

Honeywell Experion LX Specifications

General IconGeneral
BrandHoneywell
ModelExperion LX
CategoryControl Systems
LanguageEnglish

Related product manuals