3. Follow the instructions associated with the current step.
4. After you have completed the instructions confirm that you have completed the step.
5. Repeat for each step of the sequential control module.
Alert Summary overflow
The Alert Summary count is combined with the Alarm Summary count and has a maximum
limit of 14999 alarm and alert notifications. If a notification is generated when the Alert
Summary is full, one alarm or alert will be discarded (based on certain criteria) to
accommodate the new notification. Generally, alerts are discarded before alarms and low
priority alarms are discarded in deference to similar higher priority alarms.
When alarm (or alert) 15000 is generated, the alarm indicator on your Station status bar will
change to OVERFLOW.
In addition to the alarm overflow indicator, a Recover Alarms button will appear on the
corresponding summary display. If an alarm overflow occurs on a cluster server, all
associated Console and Flex Stations will also display the OVERFLOW indication and the
Recover Alarms button. If an alarm overflow occurs on a Console Station, only the Console
Station will display the overflow indicators.
Responding to alerts
Honeywell 2017 195