To reset statistics on the Meter Detail display
1. Call up the meter in the Meter Detail display.
2. Click Reset statistics.
All counters are reset to zero. The Last reset at field updates with the current date and
time.
Requesting a manual collection of data from an EFM meter
This task requests the system to collect data from the meter outside of its regular collection
schedule. It collects all data since the last successful collection. Use this task when
commissioning the meter or when a previously failed meter comes back online.
Requesting a manual collection does not affect upcoming collection schedules. For example,
if a request for all data is made at 11:00 PM and the next full collection is scheduled for
midnight, the scheduled collection will still take place at midnight.
Prerequisites
The meter must be enabled. Otherwise, this option is disabled.
To request a manual collection of data from an EFM meter
1. Call up the meter in the Meter Detail display.
2. Click Request latest data from meter.
The system requests a full collection of all data since the last successful collection.
Requesting a manual export of data from an EFM meter
Choose one of the following export tasks:
Export
task
Description
Latest
collected
data
This task requests the system to export all collected data from the meter that was not
previously exported.
Use this task when commissioning the meter to test that data export is working
correctly, or when a successful data collection fails to export.
All
collected
data from
a
specified
This task requests the system to export all collected data from the meter from a
specified date. You can choose any date from today until the last 31 days. After 31
days, data is automatically deleted (aged-out).
Use this task when data has been successfully exported but has since been lost and
Using EFM meters
Honeywell 2017 243

Table of Contents

Other manuals for Honeywell Experion LX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Experion LX and is the answer not in the manual?

Honeywell Experion LX Specifications

General IconGeneral
BrandHoneywell
ModelExperion LX
CategoryControl Systems
LanguageEnglish

Related product manuals