Item Description
Timestamps
PV Last
Processed
The time that the PV was last processed.
PV Last
Scanned
For OPC interfaces, the field timestamp for the value.
For non-OPC interfaces, the server timestamp when data was last received for this
parameter.
Alarms tab
Item Description
State alarms
State Lists each state and its name.
Enable
Alarm
Enable and disables alarms for each state.
To enable and disable alarms for the entire point, select the Alarms enabled check
box on the General tab.
Priority
Lists the priority of the alarm.
Options, in order from the lowest priority, are:
n Journal
n Low
n High
n Urgent
If critical alarm support has been enabled, urgent priority alarms with a sub priority
of 15 will be shown as critical priority alarms on the Alarm Summary and other
displays. For information about how to enable critical alarms, see Customizing
alarm colors in the Station Configuration Guide.
On Delay
(sec)
The delay time (in seconds) that must pass before an alarm is raised.
Off Delay
(sec)
The delay time (in seconds) that must pass before an alarm returns to normal (RTN).
Subpriority
The optional sub-priority level of the alarm, between 0 (lowest and default) and 15
(highest).
Re-Alarm
If selected, an alarm is raised whenever the PV changes to another alarm state.
Displaying detailed process information
Honeywell 2017 215

Table of Contents

Other manuals for Honeywell Experion LX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Experion LX and is the answer not in the manual?

Honeywell Experion LX Specifications

General IconGeneral
BrandHoneywell
ModelExperion LX
CategoryControl Systems
LanguageEnglish

Related product manuals