COMMISSIONING
146 Service Manual Part No.: 4417340 Revision 1
954 SmartServo FlexLine
Name Explanation Value Range Default
[Gas immersion depth]
The minimum required
distance below an element
before it is taken into
account in the average
Vapour temperature
calculation
floating point number:
<-x.x .. +x.x>
<0.5>
[High High alarm]
[High Alarm]
[Low Alarm]
[Low Low alarm]
4 Thresholds for activating
a related alarm status in the
Primary Value
floating point numbers:
<-x.x .. +x.x>
<+1.0E22>
[Alarm test enable]
Enables (if activated, see
next listed entity) the
simulation of one of the 4
alarms for a minute, by
simulating the actual
measured Primary Value is
below or above the alarm
threshold.
<enable>
<disable>
<disable>
[Alarm test]
Activates and selects at the
same time the Alarm test (if
enabled with the [Alarm test
enable] listed before, and the
4 alarm thresholds are
properly set).
[No Alarm]
[High High alarm]
[High Alarm]
[Low Alarm]
[Low Low alarm]
<No Alarm>
[Function identification]
The name of the current
function of this module.
This name is visible on the
HART SmartView.
13 characters
<Vapour temp.>