COMMISSIONING 
 
Part No.: 4417340 Revision 1  Service Manual    163 
  954 SmartServo FlexLine 
 
 
Rex 
 
AI 
 
HART 
 
AO 
 
Relay  Temp 
Possible combinations of cards in 
FlexLine Gauge 
Option 9  1  1  1  0  6 or 14  Option1: HRT-1(HART, Temp & AI as HART 
input), HCI-HAO (AO) - (2 cards) 
Option2: HRT-1(HART, Temp & AI as HART 
input), HCI-HAO (AO), FII-RTD (Temp) - (3 
cards) 
Option3: HRT-1(AI1), HRT-2(AI2),HCI-HAO 
(AO), FII-RTD (Temp) - (4 cards) 
 
SMV card (Display) option 3 NOT possible  
Option 10  1  0  1  0  6 or 14  Option1: HRT-1 (Temp & AI1 as HART 
input), HAO (AO) -  (2 cards) 
Option2: HRT-1 (AI1), HAO (AO), FII-RTD 
(Temp) -   (3 cards) 
Option 11  0  1  1  0  6 or 14  Option1: HRT-1 (HART & Temp), HAO (AO) 
-  (2 cards) 
Option1: HRT-1 (HART), HAO (AO) , FII- 
RTD (Temp) -   (3 cards) 
 
7.3.10.3.2  Saving configuration in database 
 
Save the configuration settings in the database to upload the same 
configuration after inserting TRL/2 card in the gauge. 
To save the configuration settings in the database: 
1.  On  the  Rosemount TankMaster  page,  select the  device 
(for  which data must to be saved) on the left pane. For 
Example: Select 
LT-52
 
2.  Right click the selected device.  The page appears as 
follow: