COMMISSIONING 
 
 
114  Service Manual    Part No.: 4417340 Revision 1 
  954 SmartServo FlexLine
 
7.3.7.3  Software Specifications 
 
7.3.7.3.1  General 
The main function of the FCI-HT software is to measure HIMS product 
density, by connecting the FCI-HT board via the HART bus to 2 
pressure sensors (P1 and P3), and via the FlexConn bus to a product 
level sensor and an optional water level sensor. 
The  alternative function  is  to  connect up  to  5  generic HART  devices 
operating in multi-drop  digital mode or 1 generic  HART  device 
operating in analog mode. 
The  FCI-HT  software  only  supports  HART  devices  with  the  following 
addresses. 
HART Address  Function 
00  Reserved for HART device in analog mode 
01  Reserved for P1 pressure sensor 
02  N/A Reserved for future use 
03  Reserved for P3 pressure sensor 
04  HART generic sensor 
 
HART Address  Function 
05  HART generic sensor 
06  HART generic sensor 
07  HART generic sensor 
08  HART generic sensor 
09  HART generic sensor 
10  HART generic sensor 
11  HART generic sensor 
12  HART generic sensor 
13  HART generic sensor 
14  HART generic sensor 
15  HART generic sensor 
 
Table 7-2  Accepted HART addresses 
☛ Before  proceeding  with  commissioning,  first  check  the  maximum 
start-up current of all connected HART devices. 
☛ Make sure the HART address of the installed device(s) are in 
accordance with Table 7-2 
Accepted HART addresses.