COMMISSIONING
78 Service Manual Part No.: 4417340 Revision 1
954 SmartServo FlexLine
7.3.4.10 Special commands
Name Value Range Default Value Explanation
[Interface 1]
This command activates
the Servo to search for
interface 1, the so called
vapor-product interface,
typically called the
product level. It uses
[Setpoint 1] and
[Integration time 1]
settings.
[Interface 2]
This command activates
the Servo to search for
interface 2, the so called
product with density A-
product with density B
interface, typically called
the interface 2 level. It
uses [Setpoint 2] and
[Integration time 2]
settings.
[Interface 3]
This command activates
the Servo to search for
interface 3, the so called
product-water interface,
typically called the water
level. It uses [Setpoint 3]
and [Integration time 3]
settings.
[Dip mode]
This command will set the
displacer at some
distance [Dip Height]
above the interface 1.
After some time [Dip time]
the interface 1 is
searched/dipped and the
displacer will return back
to the dip height position.

Table of Contents