Name Value Range Default Value Explanation
[Lock test stop level] <0.0>
Determines the level to which
the displacer goes after a
Lock to level, Lock test to
level or Test command.
[Lock to level]
This command sends the
displacer to the [Lock test
stop level] and remains
there.
[Lock test to level]
This command sends the
displacer to the [Lock test
stop level] and when
reached, issues an Unlock
command and the displacer
returns to the selected
interface.
[Test]
This command sends the
displacer to the [Lock test
stop level] and when
reached, issues a Block
command and after some
time issues an Unlock
command and the displacer
returns to the selected
interface.
[Water interface dip]
This command searches for
the water level and after that
returns to the default
operation mode.
[CIU water interface
dip]
This command searches for
the water level and stays
there.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell FlexLine SmartServo 954 and is the answer not in the manual?

Honeywell FlexLine SmartServo 954 Specifications

General IconGeneral
BrandHoneywell
ModelFlexLine SmartServo 954
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals