COMMISSIONING 
 
Part No.: 4417340 Revision 1  Service Manual    153 
  954 SmartServo FlexLine 
NOTE: Commands used in the following calibration procedure can be 
executed either by using the CAN tool, the HART SmartView, or 
Engauge. 
Calibrate the analog output of the HCI-HAO as follows: 
☛ Connect loop resistor at connector CN2 
☛ Power up HCI-HAO board 
☛ Give command [Enter Calibration Mode] 
☛Give command [Calibrate Analog Output at 4mA] 
☛ Measure  actual  output  current  through  the  loop  resistor,  using  a 
current meter 
☛ Enter this value in the [Analog Output at 4mA] entity 
☛ Give command [Calibrate Analog Output at 18mA] 
☛ Measure  actual  output  current  through  the  loop  resistor,  using  a 
current meter 
☛ Enter this value in the [Analog Output at 18mA] entity 
☛ Give command [Exit Calibration Mode], to exit the calibration mode 
These calibration data are used to calculate the analog output current 
for the Primary Value (PV). 
Until calibration has been carried out, the Health status of the PV and 
the analog output function will be: 
 
Status 
<BAD> 
Status Category 
<STATUS_CATEGORY_BAD_GENERAL_CALIBRATION_FAIL> 
Status Code 
<CALIBRATION_SET_POINTS_NOT_CALIBRATED>