COMMISSIONING
224 Service Manual Part No.: 4417340 Revision 1
954 SmartServo FlexLine
Name Value Range Default Value Description
[Contact 2
hysteresis]
< 0 – 3.402823 × 10
38
>
(meters)
< 0.010 > A value relative to the
threshold that will determine
the point at which
deactivation of a contact 2
safe state occurs after
activation by an overfill or
underfill condition.
For an underfill, deactivation
occurs when the product
level is above (threshold +
hysteresis).
For an overfill, deactivation
occurs when the product
level is below (threshold –
hysteresis).
[Contact 2
safety function
status]
(RO)
Status:
< H >, < O >, < U >, < W >
Status Code:
Defined in Section 7.3.13.1
Status:
< H >
Status Code:
NO ERROR
H: Healthy
O: Overfill condition
U: Underfill condition
W: Warning condition, safe
state is active or proof test is
overdue
[Contact 2
safety shutdown
counter]
(RO)
< 0 – 3.402823 × 10
38
>
< 0 > The number of contact 2 safe
state activations that have
occurred since
commissioning.
[Contact 2
safety shutdown
reason]
(RO)
Safety Function Status Code NO ERROR The safety function status
code identifying the reason
for the last time a contact 2
safe state activation
occurred.